Event Power Calculator

Balance loads over three phases: neutral, breaker, cable drop, generator and CEE outlets

🔒 Your data stays in your browser: nothing you type or upload is sent to a server.

How it works

Single-phase loads are sorted from largest to smallest and each is put on the least loaded phase, which balances them far better than filling L1 first. Phase currents are added as phasors 120° apart, so the neutral current is the real vector sum rather than a guess: three equal loads give zero, one loaded phase gives the whole current. This is an estimating aid for planning an event power drop. Breaker, cable and generator sizes here are not a design: the installation must be checked against AEA 90364 (IEC 60364) by someone qualified.

Formula

I = P / (V·cos φ) (1~) I = P / (√3·V_LL·cos φ) (3~) I_N = |I1∠0° + I2∠−120° + I3∠120°| ΔV = I·(R·cos φ + X·sin φ)

Common questions

Why is the generator bigger than the total kVA?

A three-phase generator supplies a third of its rating on each phase. If one phase carries more than the others, that phase hits its limit first, so the size has to cover three times the busiest phase, plus the margin.