4–20 mA Signal Scaling
Convert 4–20 mA and 0–10 V to process units and PLC counts, with NAMUR limits, square-root flow and loop burden
🔒 Your data stays in your browser: nothing you type or upload is sent to a server.
Convert 4–20 mA and 0–10 V to process units and PLC counts, with NAMUR limits, square-root flow and loop burden
🔒 Your data stays in your browser: nothing you type or upload is sent to a server.
Pick the signal, give it a process range and one known value, and the other two (signal, process value, PLC counts) follow, with the smallest step your converter can resolve in engineering units and in µA or mV. Cards disagree on where the 4 mA point lands, so choose whether counts start at the range minimum (Siemens: 4 mA = 0, 20 mA = 27648) or at 0 mA. The Structured Text lines use your own numbers.
PV = Min + (x − x0) × (Max − Min) / (x1 − x0) flow = Qmax × √(ΔP / ΔPmax) NE43 reserves the 4–20 mA signal for measurement between 3.8 and 20.5 mA. Currents of 3.6 mA or less, or 21 mA or more, are failure signals from the transmitter, and the bands in between are under/over range. A current near 0 mA usually means a broken wire or no power.
Near zero the square root is extremely steep: a tiny ΔP noise or offset becomes a large apparent flow (1 % of ΔP is 10 % of flow). The cutoff forces the flow to zero below a chosen ΔP so a stopped line does not read flow.