4–20 mA Signal Scaling

Convert 4–20 mA and 0–10 V to process units and PLC counts, with NAMUR limits, square-root flow and loop burden

🔒 Your data stays in your browser: nothing you type or upload is sent to a server.

How it works

Pick the signal, give it a process range and one known value, and the other two (signal, process value, PLC counts) follow, with the smallest step your converter can resolve in engineering units and in µA or mV. Cards disagree on where the 4 mA point lands, so choose whether counts start at the range minimum (Siemens: 4 mA = 0, 20 mA = 27648) or at 0 mA. The Structured Text lines use your own numbers.

Formula

PV = Min + (x − x0) × (Max − Min) / (x1 − x0) flow = Qmax × √(ΔP / ΔPmax)

Common questions

What do the NAMUR NE43 thresholds mean?

NE43 reserves the 4–20 mA signal for measurement between 3.8 and 20.5 mA. Currents of 3.6 mA or less, or 21 mA or more, are failure signals from the transmitter, and the bands in between are under/over range. A current near 0 mA usually means a broken wire or no power.

Why do I need a low-flow cutoff with square-root extraction?

Near zero the square root is extremely steep: a tiny ΔP noise or offset becomes a large apparent flow (1 % of ΔP is 10 % of flow). The cutoff forces the flow to zero below a chosen ΔP so a stopped line does not read flow.