RTD and Thermocouple Tables

Pt100, Pt500 and Pt1000 per IEC 60751 and NIST thermocouples K, J, T, E, N, S, R, B, in both directions with cold-junction compensation

🔒 Your data stays in your browser: nothing you type or upload is sent to a server.

How it works

RTDs use the Callendar–Van Dusen equation with the IEC 60751 coefficients, inverted in closed form above 0 °C and by Newton iteration below. Thermocouples use the NIST ITS-90 reference polynomials for types K, J, T, E, N, S, R and B (all eight), inverted numerically, with cold-junction compensation: the voltage at your instrument plus the voltage of the cold junction gives the hot-junction temperature. Type B is inverted only from 250 °C, where its voltage is monotonic.

Formula

R(t) = R0 (1 + A t + B t²) (t ≥ 0) · R(t) = R0 [1 + A t + B t² + C (t − 100) t³] (t < 0)

Common questions

Why does a 2-wire Pt100 read high?

The instrument measures the sensor plus both leads in series. At about 0.39 Ω per °C for a Pt100, every ohm of lead resistance reads as 2.6 °C. 3-wire circuits measure one lead to cancel it, and 4-wire circuits remove the leads entirely.

Do I compensate the cold junction in the PLC or in the transmitter?

Wherever the thermocouple wire ends in copper. Measure the temperature of that terminal block and add the voltage for that temperature to your reading, exactly what the "cold junction" field does here.