Server Rack Planner (3D)
Fill a 3D rack with servers, switches and panels: power, heat in BTU/h, air needed, circuit check and UPS load
🔒 Your data stays in your browser: nothing you type or upload is sent to a server.
Fill a 3D rack with servers, switches and panels: power, heat in BTU/h, air needed, circuit check and UPS load
🔒 Your data stays in your browser: nothing you type or upload is sent to a server.
Build a server rack in 3D: choose its height in units (U), add servers, storage, switches and blanking panels, and give each one its power. The tool stops devices from overlapping, adds up the watts, converts them into heat (BTU/h and cooling tons) and into the air that has to flow through the rack for a temperature rise you choose. It checks the current against the circuit (the continuous limit is 80 percent of the breaker) and, if you enter the rating of your UPS, its load and best-case runtime. The heat view colors every device by watts per unit so the dense spots stand out. The plan is saved in this browser and can be downloaded as a file. The typical watts are plain starting values to replace with the label figures.
BTU/h = W x 3.412 cooling tons = BTU/h / 12000 air (CFM) = 1.76 x W / rise (°C) amps = W / volts circuit limit = breaker x 0.8 1 U = 44.45 mm It depends on two limits you can check here. The electrical one: a circuit should carry no more than 80 percent of its breaker continuously, so a 16 A breaker at 230 V gives about 2.9 kW. The thermal one: all of that power ends up as heat, and the room must remove it, roughly 3.4 BTU/h per watt. Many ordinary rooms with plain air cooling are planned around a few kilowatts per rack, and dense racks of GPU servers can pass that quickly. The tool warns when the load passes the circuit limit and when the rack goes beyond a few kilowatts, as a prompt to plan the cooling, not as a rule.
Servers pull cool air in at the front and blow warm air out the back. An empty unit between two devices lets warm air flow back to the front and be drawn in again, which raises the temperature of the intake. A 1U blanking panel closes the hole. The tool counts empty units sitting between devices and suggests panels for them; free space above the top device is not counted.